CSS Series 110D Type 010 A/B

Conveyor system interrupted in closing area 

gte – Conveyor System Shutter (CSS) T90/EI90 (EI120)*  

 

Proofs of suitability*:  
Z-6.6-2089 General Technical Approval of the German Institute for Structural Engineering / Deutsches Institut für Bautechnik (DIBt), Berlin (Germany). 
LPCB 735a

Loss Prevention Certification Board,

of BRE London (Great Britain Commonwealth) 

ETA-12/0002

European Technical Approval (Europe) 

TP 0620928

т Сертификата пожарной безопасности (Russia) 

AEAI 18945

VKF Fire Protection Practice (Switzerland) 

FAA Baureihe 110D Typ 10 A/B 
 

Application 

The conveyor system is interrupted in the closing area or it is interruptible .

 

Clear wall opening

W = 500 mm up to 2.500 mm

H = 500 mm up to 2.500 mm

Thickness of the closing element = 38 mm

W = 2.500 mm* up to 4.000 mm*

H = 2.500 mm* up to  4.000 mm*

Thickness of closing element  = 58 mm

 

Closing direction

←   →    ↑    ↓    →←

 

Kind of installation

Raised or floor-level installation on walls possible. 

 

Mounting on: 

Concrete, brickwork, gas concrete, prefabricated walls, cladded steel structure,* 

 

Design

Type

010 A

010 B

operating type

manually

automatic

operating position

systematically open

open / closed

open

manually operated

motor driven

close

manually operated

automatic

alarm closing

in the event of fire through mechanical closing device

 

Operating Principles 

During conveying operation of the conveyor system the closing element is situated next to, above or below the opening and is retained there by means of the hold-open device (magnetic clamp).

 

In the event of a fire detection the closing element moves into the gap of the conveyor system situated in front of the opening, driven by mechanically stored energy and seals it all over, four-sided overlapping and without any residual openings.

 

In case of a motor-driven design all functions can be operated by remote control via control of the hold-open device, the manual local push button on the CSS or by means of the conveyor system control unit. 

 

Equipment *

Basic equipment see „Description of Conveyor system shutters"

- Hold-open device for keeping the CSS open

- Sensor for realizing the open position.

- Terminal box as interface for control. 

 

Additional equipment* 

- Tilting bridges with supporting roller 

 

*) Detailed definitions can be taken from the approvals (upon request) 