FAA Series 110D Type 100 A/B

Conveyor System not interrupted in closing Area  

gte – Conveyor System Shutter (CSS) T90/EI90 (EI120)* 

Proofs of suitability*

Z-6.6-2089 

 

General Technical Approval of the German Institute for Structural Engineering / Deutsches Institut für Bautechnik (DIBt), Berlin (Germany)  

LPCB 735a 

 

Loss Prevention Certification Board, from BRE London (Great Britain Commonwealth) 

ETA-16/0852 

 

European Technical Approval (Europe) 

TP 0620928 

 

Сертификата пожарной безопасности (Russia) 

 Baureihe 100 - Typ 101


 

Application

The conveyor system is not interrupted in the closing area.

 

Conveyor system

Roller, chain, belt conveyor, Power & Free plant, electrified hanging monorail system, etc. * 

Aluminum capping beams in closing area shall be separated by cutting them thermally.* 

 

Clear wall opening  

(not height above conveyor system )
W = 500 mm up to 2.500 mm

H = 500 mm up to 2.500 mm

Thickness of closing element  = 38 mm


W = 2.500 mm* up to 4.000 mm*

H = 2.500 mm* up to 4.000 mm*

Thickness of closing element  = 58 mm 

 

Closing direction

←    →     ↓    →← 

 

Kind of installation

Raised or floor-level installation on walls possible. 

 

Mounting on

Concrete, brickwork, gas concrete, prefabricated walls, cladded steel structure,* 

 

Design

Type

100 A

100 B

operating type

manually

automatic

operating position

systematically open

open/closed

open

manually operated

motor driven

close

manually operated

automatic

alarm closing

in the event of fire through mechanical closing device 

 

Operating Principles

During conveying operation of the conveyor system the closing element is situated next to or above the opening and is retained there by means of the hold-open device (magnetic clamp). In the event of fire detection the closing element, whose sealing elements are adjusted to the profile of the conveyor system, moves, driven by mechanically stored energy, as close as possible towards the continuous conveyor system. The closing element seals the opening three-sided overlapping. Remaining openings are closed through the exposure to fire.

In case of a motor-driven design all functions can be operated by remote control via control of the hold-open device, the local manual push button on the CSS or by means of the conveyor system control.  

 

Equipment

- Basic equipment see  "Description of onveyor system shutters "
- Hold-open device for keeping the CSS open 
- Sensor for realizing the open position. 
- Terminal box as interface for control. 

 

Additional Equipment

- Clearing device 
- stopper 

 

*) Detailed definitions can be taken from the approvals (upon request) 

gte Brandschutz gte Brandschutz